Cassette Air Conditioner (FCQF Series)

Step into the next generation, technology-enabled cassette air conditioners by Daikin. The advanced built-in features will make you save more energy while enjoying the comfortable power chill home cooling. Experience even airflow that is personalized according to your space with high-powered sensors that detect the cooling requirements of your place. These state-of-the-art cassette air conditioners by Daikin offer a unique lifestyle with ultra-modern and holistic air conditioning.

SKU: FCQF Series Category:

Specification

Ceiling Mounted 3 x 3 Cassette Type (Cooling Only)

Model Indoor unit FCQF18ARV16 FCQF24ARV16 FCQF30ARV16 FCQF36ARV16 FCQF42ARV16 FCQF48ARV16
Outdoor unit RGVF18ASV16 RGVF24ASV16 RGVF30ASV16 RGVF36ASV16 RGVF42ASY16 RGVF48ASY16
Remote Controller Wireless ARC91A151
Wired NA
Panel Code Model Number BYCQ48EAF6
Power supply kw 1 Phase, 230 V, 50 Hz 1 Phase, 230 V, 50 Hz 1 Phase, 230 V, 50 Hz 1 Phase, 230 V, 50 Hz 3 Phase, 415 V, 50 Hz 3 Phase, 415 V, 50 Hz
Cooling capacity kW 5.30 7.03 8.79 10.50 12.31 13.36
Power consumption Cooling-Rated Watt 1452 1926 2410 3040 3800 4200
Annual Power Consumption Cooling-Rated kWh 1124 1491 1866 2353 NA* NA*
ISEER / Stars Wh/Wh 3.65/3 Star 3.65/3 Star 3.65/3 Star 3.45/2 Star 3.23/*NA 3.18/*NA

Indoor unit

Airflow rate (H/HM/M/ML/L) m3/min (H)23 (HM)21 (M)18.5 (ML)16
(L)13.5
(H)23 (HM)21
(M)18.5 (ML)16
(L)13.5
(H)34.5 (HM)31
(M)27.5 (ML)24
(L)20
(H)34.5 (HM)31
(M)27.5 (ML)24
(L)20
(H)36.5 (HM)33
(M)29 (ML)25 (L)21
(H)36.5 (HM)33
(M)29 (ML)25
(L)21
cfm (H)812 (HM)742
(M)653 (ML)565
(L)477
(H)812 (HM)742
(M)653 (ML)565
(L)477
(H)1218
(HM)1095 (M)971
(ML)848 (L)706
(H)1218
(HM)1095(M)971
(ML)848(L)706
(H)1289 (HM)1165
(M)1024 (ML)883
(L)742
(H)1289 (HM)1165
(M)1024 (ML)883
(L)742
Sound level (H/HM/M/ML/L) dB(A) 37/34.5/32/ 29.5/27.5 37/34.5/32/ 29.5/27.5 45/41.5/38/35/32.5 45/41.5/38/35/32.5 46/43/40/36/32.5 46/43/40/36/32.5
Dimensions Unit (HXWXD) mm 256x840x840 256x840x840 298x840x840 298x840x840 298x840x840 298x840x840
Dimensions Panel (HXWXD) mm 50x950x950 50x950x950 50x950x950 50x950x950 50x950x950 50x950x950
Machine weight kg 22 22 25 25 25 25
Panel weight kg 5.5 5.5 5.5 5.5 5.5 5.5

Outdoor unit

Compressor Type Rotary Rotary Rotary Rotary Rotary Rotary
Refrigerant R-32 R-32 R-32 R-32 R-32 R-32
Refrigerant charge (R-32) kg 1.09 (Charged For 7.5 m) 1.21 (Charged For 7.5m) 2.21 (Charged For 7.5m) 2.64 (Charged For 7.5m) 2.05 (Charged For 7.5m) 2.07 (Charged For 7.5m)
Sound level Cooling dB(A) 50 56 58 58 58 60
Dimensions (HXWXD) mm 595x845x300 595x845x300 990x940x320
Machine weight kg 40 46.5 68 71 74 74
Certified operation range °CDB 19 to 48 19 to 48 19 to 48 19 to 48 19 to 48 19 to 48
Piping connections Liquid (Flare) mm Ø6.35 Ø6.35 Ø9.5 Ø9.5 Ø9.5 Ø9.5
Gas (Flare) mm Ø12.7 Ø15.88 Ø15.88 Ø15.88 Ø15.88 Ø15.88
Drain mm Ø26(Hole) Ø26(Hole) Ø26(Hole) Ø26(Hole) Ø26(Hole) Ø26(Hole)
Std. interunit piping length m 7.5 7.5 7.5 7.5 7.5 7.5
Max. interunit piping length m 20 20 20 20 30 30
Max. installation level difference m 10 10 10 10 15 15

Note :

  • Rated cooling capacities are based on the following conditions: Return air temp.: 27°CDB, 19.0°CWB, Outdoor temp.: 35°CDB, 24ºCWB Equiv. ref. piping: 7.5m (Horizontal)
  • Anechoic chamber conversion value, measured under JIS conditions. During actual operation, these values are normally somewhat higher as a result of ambient conditions.