Specification
High Static Duct Type (Cooling Only)

5.5TR | 8.5TR | 11.0 TR | 10.8 TR | 16.5 TR | ||||
Model | Indoor Unit | FDR65FRV 16 |
FDR100FRV 16 |
FDR130FRV 16 |
FDR130FRV 162 |
FDR200FRY 16 |
||
Outdoor Unit | RR65FRY 16 |
FDR100FRY 16 |
RR130FRY 16 |
RR65FRY 16(2Nos) |
RR100FRY 16(2Nos) |
|||
Nominal Cooling Capacity | Btu/Hr | 66000 | 102000 | 132000 | 129600 | 198000 | ||
KW | 19.3 | 29.9 | 38.7 | 38 | 58 | |||
Actual Capacity | % | Minimum 90% of Nominal Capacity | ||||||
Nominal Total Input Power (Cooling) | W | 6400 | 11000 | 14600 | 13000 | 21600 | ||
Running Current | A | 11 | 19 | 23 | 22 | 38 | ||
Power Source | V/Ph/ Hz |
415/3/50 | ||||||
Refrigerant Type | – | R-410A | ||||||
Indoor unit | ||||||||
---|---|---|---|---|---|---|---|---|
Control | Operation | – | Wired Control | |||||
Air Flow | High | cfm | 2200 | 3400 | 4400 | 4400 | 6600 | |
Medium | cfm | 2045 | 3100 | 3850 | 3850 | 5800 | ||
Low | cfm | 1890 | 2800 | 3330 | 3330 | 5000 | ||
Static Pressure | High | Pa | 50 | 50 | 60 | 60 | 80 | |
Sound Pressure Level (H) | dBA | 51 | 52 | 54 | 54 | 59 | ||
Unit Dimension | Height x Width x Depth |
mm | 450×1170 x700 |
450×1660 x700 |
470×1700 x940 |
470×1700 x940 |
590×1885 x1145 |
|
Packing Dimension | Height x Width x Depth |
mm | 465×1370 x720 |
585×1880 x740 |
620×1930 x990 |
620×1930 x990 |
755×2130 x1250 |
|
Unit Weight | kg | 60 | 95 | 125 | 130 | 175 | ||
Condensate Drain Size | mm | 40.5 | ||||||
Outdoor unit | ||||||||
Unit Dimesion | Height x Width x Depth |
mm | 930×1025 x410 |
930×1200 x550 |
930×1650 x620 |
930×1025 x410 |
930×1200 x550 |
|
Packing Dimension | Height x Width x Depth |
mm | 1080×1170 x470 |
1080×1350 x620 |
1088×1846 x720 |
1080×1170 x470 |
1080×1350 x620 |
|
Unit Weight | kg | 96 | 147 | 173 | 96 | 147 | ||
Pipe Connection |
Type | – | Liquid (Flared) & Gas (Brazed) | |||||
Size | Liquid | mm | 12.7 | 12.7 | 15.9 | 12.7 | 12.7 | |
Gas | mm | 22.2 | 28.6 | 28.6 | 22.2 | 28.6 | ||
Refrigerant Pre-Charged (At 7.5m Pipe Length) |
kg | 4.4 | 5.7 | 8 | 2X4.4 | 2X5.9* |
Note :
- All specifications are subject to change by the manufacturer without prior notice.
- Cooling capacity is based on the conditions below:
Cooling – 27°C DB / 19°C WB indoor and 35°C DB outdoor. - Refrigerant (R-410) is pre-charged at factory shipment (Outdoor Unit).